Documentation for fire doors and fire sliding doors
Fire sliding doors and external hinged fire doors
Fire sliding doors and external hinged fire doors must be approved in accordance with EN 16034
Classification report in accordance with EN 13501-2 for
EI160-C / EI260-C fire sliding door
The fire sliding doors are tested and approved with the following options:
- Automatic control
- Photocells in front edge of door leaf
- Photocells in frame legs (max. 3 sets)
- Brakes
- Pedestrian door with level-free access (can be used as an escape route) with a max. clear opening of 800x2055 mm (WxH)
- Window in pedestrian door, max. 200x400 mm
- Pedestrian door switch
- Window, max. 400x700 mm
- Installation in concrete wall (min. 150 mm)
- Installation in panel wall (EI60 min. 100 mm)
- Door magnet (e.g. for ABDL)
- Kick plates, max. 800 mm
- Painting of door leaf and frame
- Frame, 4 sides, and door installation above floor
- Rail casing
- Silicone strips along sides and top
- Wall guide (instead of bottom guide)
- External locks
- Split frame
Approval for:
Fire sliding doors, door, 1 leaf, size up to interior dimensions of 3700x4600mm (WxH)
Certificate for fire sliding doors approved in accordance with EN 16034
Classification report in accordance with EN 13501-2 for:
EI260-C hinged fire door
The 1-leaf and 2-leaf hinged doors are tested and approved with the following options:
- Window, max. 600x800 mm, with break-in proof installation on the front
- Double glazing
- Installation in concrete wall (min. 150 mm)
- Installation in plasterboard wall (EI60)
- Installation in panel wall (EI60 min. 100 mm)
- Silicone seals
- Doorstep
- Frame 4 sides
- Installation above floor level (height unlimited)
- Hot wire in frame
- Extra lock / night lock
- Kick plates, max. 800 mm
- Painting of door leaf and frame
- Extra security lock for large doors
- Door magnet (e.g. for ABDL)
- Pneumatic door control
- Switch (externally mounted)
- Door selector (for double-leaf doors)
- Automatic control with radar
- Dog bolts
- Panic bar
- Cable loop (on the rear edge of the door leaf as well on the front of the door leaf)
Approval for:
Doors, 1-leaf, min. size 232x654 mm (WxH), max. size 1405x2950 mm (WxH), though max. 3.46 m2 (clear openings).
Doors, 2-leaf, min. size 984x1905 mm (WxH), max. size 2200x2300 / 1968x2540 mm (WxH) (clear openings).
Certificate for fire doors approved in accordance with EN 16034
Internal hinged fire doors and fire sliding doors mainly for pedestrian use
Internal hinged fire doors must still be approved according to DS 1052.2. Also sliding fire doors mainly intended for pedestrian use can be approved according to DS 1052.2.
Certificate is valid for:
BD30 hinged door, 1 leaf
BS60 hinged door, 1 leaf, size up to interior dimensions of 1016x2100mm
BS60 hinged door, 2 leafs, size up to interior dimensions of 2035x2100mm
BS60 sliding door, 1 leaf, size up to a wall opening of 4800x3600mm, corridor door up to a size of 1016x2061mm
Approval for:
BS60 hinged door, 1 leaf, good as chill door, size up to interior dimensions of 1126x2363 mm
BS60 hinged door, 2 leafs, good as chill door, size up to interior dimensions of 2259x2363 mm